Adding a BACnet or Modbus connector
A connector polls one controller on a building network and sends its
points to Baler. It runs on a Windrow edge node: the Windrow beside
Baler, or one on a site gateway such as a Raspberry Pi
(Edge nodes). You manage connectors on the
Connectors page (/ui/connectors.html, Connectors in the top
navigation).
One connector is one piece of equipment. Its topic prefix, such as
fbf/home/ahu-1, becomes the equipment's id in Baler, and each point is
published under it, for example fbf/home/ahu-1/zone-temp.
Remote systems that already store data (SkySpark, SQL, weather) are Sources, not connectors.
Who can do what
Every signed-in user can see edge nodes, connectors, their status and the devices found. Only an admin can add, edit or delete connectors, run scans, and set device logins. Other roles see the page without those buttons, with the note Ask an admin to add or change connectors.
Pick an edge node
The Edge nodes row at the top lists every node Baler can reach:
- Windrow beside Baler: the
windrow_apicontainer, set byWINDROW_API_URLin.env(thedeploy/nash-srv/docker-compose.windrow.ymloverlay sets it for you). - A remote node (
<site> / <instance>): a Windrow that publishes a status heartbeat over MQTT with its edge account (Edge nodes).
Each node shows a green (online) or red (offline) dot, when it was last
seen, and how many new devices it has found. Click a node to select it; the
page remembers it in the address (#local/local).
When a node is offline, a banner says since when, its buttons are disabled, and the page stops asking it for lists until it reports in again.
The topic prefix rule
The prefix must sit under the node's allowed prefix, or the data never reaches Baler. The dialog shows the allowed prefix under the field and refuses anything else, naming the prefix it expects:
| Node | Allowed prefix | Why |
|---|---|---|
| Windrow beside Baler | fbf/ | Baler's mqtt_listener takes in fbf/# only |
| Remote node | its site's prefix, e.g. fbf/home/ | The broker drops anything a site's account publishes outside its site's prefixes |
A remote node's site is the site its broker account belongs to (Ops → Edge nodes). Baler checks the prefix again when the connector is saved, for every role and every client (the API too), and refuses one outside the node's allowed prefix. If it can't look the site up, the dialog says so under the field, and you have to make sure of the prefix yourself.
Two more rules, also checked in the dialog:
- No two connectors on a node share a prefix, and one can't sit inside
another's (
fbf/home/ahu-1andfbf/home/ahu-1/fan): their points would mix into one piece of equipment. - No spaces, no
#or+, and no leading, trailing or double/.
Add a BACnet connector
- Select the node and click + Add connector. BACnet/IP is selected.
- Enter the Device address, the controller's IP, with
:portif it isn't 47808 (e.g.192.168.1.20or172.30.0.10:47808), and the Device instance (e.g.10228). - Click Read the point list from the device, or press Enter in either field. A big controller takes a minute; the line beside the button counts the seconds, and Stop waiting gives up. The read runs on the node as a background job, so it isn't cut off however long it takes.
- Pick the points to poll:
- Search matches the name, the device's own object name, the
description, the object (
AI 3,analog-input,3) and the units. - Object type filters to AI, AO, AV, BI, BO, BV, MSI, MSO, MSV (only the types the device has, with counts).
- The header checkbox ticks or unticks every point shown; Select none clears them all. The count above the table says how many are selected (12 of 340 points selected · 40 shown).
- On a small device (50 points or fewer) every point starts ticked; on a bigger one none do, so search or filter, then tick the ones you want.
- Search matches the name, the device's own object name, the
description, the object (
- Rename points in Name in Baler if you like (e.g.
zone-tempinstead ofZN-T). The name is the last part of the point's topic, and must be unique within the connector. The device's own name and description stay visible under the field. Pressing Enter in a name does nothing. - Enter the Topic prefix (see the rule above) and Poll every (seconds, default 5).
- Click Add connector.
If you fix the address and read again, your ticks and renamed points are kept for every object the device still has.
Connectors read every point you pick. Commandable points (outputs and values
that aren't sensors) are also tagged writable, so an operator can command
them from Baler; everything else is read-only.
Add a Modbus connector
- Click + Add connector and choose Modbus TCP.
- Enter the Host (IP or name), Port (default 502) and Unit id (default 1).
- Add one row per point: a name and the holding register number, as numbered in the device's manual. + Add register adds a row.
- Click Test read. It reads the first register in the list once, before anything is saved, and shows the value (OK: zone_temp (register 0) = 70) or what went wrong (can't connect, or the device refused the register).
- Enter the topic prefix and poll interval, and click Add connector.
Modbus has no point list to read: registers are whatever the manual says. Each register is read as one unsigned 16-bit value.
Follow a device that moves (device announce)
A device on DHCP, or one that gets swapped or re-addressed, leaves a connector polling an address nobody answers on. Give the connector a Device name (for announce) in its dialog (BACnet or Modbus), and the node keeps it pointed at the device:
- Announce. A device that can run Windrow's small sender
(
python -m windrow.announce --name <name> --to <node>, orinstall-edge.sh announceon a Pi) tells its node "I am here" over UDP port 47900 every 30 s, and at once when its address changes. The node takes the address from where the datagram came from, and only from the subnets it allows. - DNS. For a device that can't run anything, use its DNS name as the device name; the node re-resolves it every few minutes.
When the address behind a device name changes, the node re-points every connector with that name, the same way an edit would. Leave the field empty to keep the address fixed. An existing BACnet connector's address can also be changed by hand in the dialog (its instance can't).
The node's card shows how many devices announced themselves and how many are
online (2 of 3 announced online), and how many announcements it refused.
Under the node, Announced devices lists each one: its name, address (and
where it moved from), services, when it was last seen, whether it's online,
and the connectors that follow it.
For the Windrow beside Baler, the deploy/nash-srv overlay publishes UDP
WINDROW_ANNOUNCE_PORT (default 47900) and hears only
WINDROW_ANNOUNCE_ALLOW (default 192.168.128.0/24): set both in .env.
Details, including signed announcements, are in Windrow's
edge-nodes guide.
Check that it's working
The Status column of the connectors table answers "is it polling?" without opening the equipment:
| Status | Meaning |
|---|---|
| Starting, no reads yet | Just added or edited; the first read hasn't happened |
| OK, last value 10:42:07 | Every point read on its last try |
| 3 of 20 failing | Some points fail; the last error and their names are shown |
| Not reading | Every point fails, e.g. the device is unreachable; the error is shown in red |
Under it: when it last polled and, if it's failing, when it last read
anything. Status is kept by the edge node since it started, and resets when
you edit the connector. A node running an older Windrow shows —.
The prefix in each row links to the equipment in Equipment
(index.html?equip=urn:equip:<prefix>), which opens the tree at it. Its
points appear there as they report.
Find a connector
With more than one connector, a Filter box above the table matches the
topic prefix and the device: type vav-42 and only fbf/vav-42 is left.
Only ones not OK narrows to connectors whose status isn't OK.
Connectors are grouped by controller, one header per device with its count
and how many aren't OK; click the header to collapse it. Within a group they
are sorted by prefix, numbers in order (vav-2 before vav-10), and a big
group shows 25 at a time with Show more. A filter shows every match.
Edit or delete a connector
Edit opens the same dialog. You can change the points, their names, the topic prefix and the poll interval.
- BACnet: the address and instance are fixed. To poll another device, add a new connector. Read the point list again to add points the device has gained: points not polled yet come back unticked, and the status line says how many.
- Modbus: the host, port and unit id can change too.
Changing the prefix moves the equipment: the old topics are cleared, and the points appear under the new prefix.
Delete asks you to type the prefix to confirm. Polling stops; history already recorded is kept.
Scan for devices
- Scan for BACnet devices sends a Who-Is from the node (broadcast, and a directed one to each device it already polls).
- Sweep a subnet for Modbus… opens a dialog prefilled with the node's own subnet (when its Windrow reports one). It probes TCP port 502 on every address in the subnet, so only sweep networks you're allowed to. Up to /22 (1,024 addresses) starts at once; /16 to /21 asks you to press the button again to confirm; anything larger is refused.
A scan runs on the node as a background job. A progress line under the toolbar counts the seconds (and, for a sweep, the addresses probed), and the scan buttons stay disabled until it finishes, so a double click can't start two. Stop waiting stops the page waiting; the node finishes the scan anyway.
Everything a scan finds appears under Devices found, as do the node's own
periodic scans (BACnet every 5 minutes; a Modbus sweep of any
--modbus-scan-cidr). A pending device isn't polled yet: click
Add connector… on its row and the dialog opens with its address filled
in. Ignore hides a device from the new ones; Restore brings it back.
Broadcast discovery doesn't cross Docker's NAT, so the Windrow beside Baler only finds devices by directed Who-Is. See Edge nodes for when you need a gateway on the site's LAN.
Device logins
Set (or Change) in a row's Login column stores a username and password for that device or connector, encrypted on the edge node. Listings only ever show the username. The dialog names the device, and stays open with an error if the save fails, so nothing you typed is lost.
A device that accepts a well-known factory login shows factory login works with a note: change the password on the device. Recheck login tests again after you have.
Try it against the mock devices
With the Windrow overlay, Baler runs a simulated BACnet controller (a mock
hospital) and you can start a simulated Modbus server inside windrow_api:
Code
Sign in at http://localhost:8080/ui/connectors.html as an admin (the first
one comes from POST /auth/orgs, see the README) and select Windrow beside
Baler.
BACnet: + Add connector, address 172.30.0.10:47808, instance
3456, Read the point list. Search for zone, tick a few points, prefix
fbf/mock/ahu-1, Add connector. Within a poll interval the row shows
OK, last value ….
Modbus: + Add connector, Modbus TCP, host 127.0.0.1, port
5020, unit 1. Rows zone_temp → register 0 and fan_status →
register 1. Test read shows zone_temp (register 0) = 70 (it cycles
69-71). Prefix fbf/mock/modbus-1, Add connector.
Scan: Scan for BACnet devices finds the mock controller (instance
3456) once a connector polls it, by directed Who-Is. Sweep a subnet for
Modbus… is prefilled with 172.30.0.0/24, the node's BACnet network; the
mock Modbus server listens on 5020, not 502, so a sweep doesn't find it. Use
a sweep on a real network.
Doing it over the API
The page calls POST /ops/edges/<site>/<instance>/actions/<action>
(ops-api-openapi.yaml,
also at /ops/docs on a running Baler), with Windrow's
command-channel action names: learn, create_connection,
modbus_create_connection, modbus_test_read, update_connection,
delete_connection, and start_job / get_job for scans and reads. The
Windrow beside Baler is local/local. See Windrow's
command channel
for each action's fields.