Fault Detection
Fault detection is fault_detector.py: a decoupled third MQTT subscriber
plus a periodic sweep of point_history, evaluating rules you configure
through the Fault API and recording open/resolved faults in
Postgres. It doesn't hook into ingest.py at all — MQTT already fans
one message out to every subscriber for free, so a second subscription
gets a live copy of every reading with zero coupling to the ingest hot
path.
Registering a rule
Code
applies_to takes exactly one of topic_glob or brick_class. See
POST /fault/rules for the full field reference and more
stuck/stale examples.
Cur mode only sees MQTT traffic. fault_detector.py subscribes to
fbf/# directly and never touches ingest_api.py — so a reading pushed
via POST /ingest/ingest (see Architecture) is stored
identically, but never evaluated by a Cur-mode rule, since it never
crosses MQTT. To trigger one for testing, publish over MQTT yourself,
same envelope POST /ingest uses:
Code
Cur vs. His — why there are two evaluation modes
Some faults are only detectable in the moment; others fundamentally need
a time window. A range check ("is this value currently outside
bounds?") only makes sense against a live reading as it arrives. A
stuck or stale check ("has this value stopped changing?", "has this
point stopped reporting?") is meaningless without looking back over
history — there's no such thing as a single reading being "stale."
So rules declare a mode:
cur— evaluated in real time, directly off the MQTT message as it arrives. Onlyrangerules run in this mode.his— evaluated periodically (every--his-intervalseconds, default 30) againstpoint_history. Onlystuck/stalerules run in this mode.
Both modes skip samples flagged bad. A reading the device marks as fault,
overridden or out of service neither opens nor resolves a Cur-mode fault,
and stuck counts only good samples. The same daemon also runs the
quality sweep (range, spike, unit), by default every 5 minutes. See
Sample quality.
One important asymmetry: a rule's topic_glob is matched against the
raw MQTT topic in Cur mode, but against the urn:point:{topic}
URI in His mode (since His-mode rules query point_history, which is
keyed by URI, not topic). This is fault_detector.py prepending
urn:point: onto your topic_glob internally before matching — write
topic_glob as the raw topic either way (e.g. "fbf/ahu-1/*", same
string a Cur-mode rule would use), never with urn:point: already on the
front yourself. Adding the prefix yourself double-prefixes it and the rule
silently matches nothing, ever — no error, just zero faults forever. Same
glob syntax, different string matched against it under the hood — worth
double-checking if a His-mode rule silently never fires.
What each rule type actually checks — and where it doesn't fire
range — faulted if the value is outside [min, max]. Only numeric,
non-boolean values can ever match: a None, a string, or a boolean value
is treated as not faulted, never as an error. That's deliberate — a
sensor going offline and reporting garbage is a different failure mode
than a real value being out of bounds, and range isn't the rule that
catches it. If you need to know when a point stops reporting sensible
values at all, that's what stale is for.
stuck — faulted if every reading in the trailing stuck_seconds
window is the same value, and at least one reading exists in that
window. A point with zero readings in the window isn't "stuck," it's
silent — again, that's stale's job, not stuck's. Pick stuck_seconds
longer than the point's natural dwell time at one value, or a
legitimately-stable-but-healthy point (an unoccupied zone's flat
temperature, say) will false-positive.
stale — faulted if the most recent reading is older than
max_age_seconds. A point that has never reported even once is not
flagged stale — there's no reliable "first seen" time to measure
staleness from, so a point that was misconfigured from day one and never
ingested anything will never trigger this rule. It only catches a point
that stops reporting after having reported at least once.
The roster is live, not configured
A His-mode rule's set of points to evaluate isn't a separate list you
maintain — it's SELECT DISTINCT point_uri FROM point_history filtered
by the rule's topic_glob. New points that start reporting are picked up
automatically, with zero additional configuration. The flip side is the
same as the stale gap above: a point that's never reported never
appears in any His-mode roster.
Severity, acknowledging, and snoozing
A rule can carry a free-form severity (e.g. "critical", "warning",
"info" — not validated or enumerated, just displayed) alongside name/
mode/type/applies_to. It's copied onto every fault that rule opens,
captured at open time — editing a rule's severity afterward doesn't
relabel faults it already raised, same as detail.
POST /fault/faults/{id}/ack and POST /fault/faults/{id}/snooze
({"minutes": 60}) let an operator acknowledge or temporarily suppress a
specific open fault. Both are pure annotation: acking or snoozing a fault
does not stop fault_detector.py from evaluating the underlying rule,
close the fault, or affect webhook delivery — a snoozed fault that's still
genuinely faulted keeps its status: open and still fires
fault.resolved normally if it clears. See POST /faults/{id}/ack for the full field reference.
GET /fault/faults lists faults newest first, one page at a time: 500 by
default, up to 5000 with ?limit=. It's still a bare JSON array; the
X-Total-Count header says how many match in all, and X-Next-Before
(absent on the last page) is the ?before= for the next page. ?since=
(ISO 8601 with an offset) narrows to faults that started after a time.
There's a small browser UI over all of this at /ui/alarms.html (through
the gateway: localhost:8080/ui/alarms.html) — a live-polling table of
faults with Ack/Snooze buttons, filterable by status, plus a "New rule"
form and a Rules table with Delete. The form has the same Form/Raw JSON
toggle as the derivation editor: Form builds the config
field-by-field with a type selector switching between range
(min/max), stuck (stuck_seconds), and stale (max_age_seconds)
fields; Raw JSON is the same underlying CodeMirror-edited object for
hand-writing or pasting a whole rule. It's a thin client over the same
API above, nothing it does isn't also reachable by curl.
Controller alarms from BACnet (Windrow forward_alarms)
A Windrow connection with forward_alarms set registers Windrow as a recipient of the controller's
own intrinsic-reporting alarms: limits, alarm states and faults the controller itself detects. It
publishes them, retained, on {topic_prefix}/{label}/alarm, or on
{topic_prefix}/alarms/{type}-{instance} for an object no connection polls. fault_detector turns
each one into a fault. No rule is needed.
- One fault per object. Its rule id is
bacnet:alarm, and its point is the polled point (or thealarms/...topic). Thebacnet:namespace means the sweep that resolves faults of deleted rules leaves these alone. - Opening and resolving. A transition to any non-normal state (or, after a Windrow restart, an
active alarm in Windrow's startup summary) opens the fault. If the fault is already open, its
detail and severity are updated instead, for example when it goes from high-limit to low-limit.
A transition back to
normalresolves it. - Webhooks.
fault.openedandfault.resolvedfire as for any rule. - Severity.
- A
faultstate iscritical. notify_typeeventisinfo.- Otherwise, BACnet priority 0-63 is
critical, and anything higher iswarning.
- A
- Alarms page. The Rule column shows "BACnet alarm (controller)". The Detail column shows the transition, the controller's message text and the object.
- Not readings. These messages aren't stored as readings;
mqtt_listenerskips them. - Ack is Baler-only. Acking in Baler doesn't acknowledge the alarm on the controller (Windrow has no AcknowledgeAlarm yet).
Fault lifecycle — transitions only
Opening a fault that's already open is a no-op (no new row, no webhook). Webhooks fire only on the not-open → open and open → resolved transitions — there are no periodic "still faulted" pings while a fault stays open. See Webhooks for delivery semantics.
Upstream: sampling and change-of-value
Fault detection evaluates whatever readings actually arrive — it has no
say over how often a point reports or which changes get published in
the first place. That's configured upstream, in Windrow's connection layer
(his_collect_cov, his_collect_interval, matching real Haystack/Haxall
semantics). See Windrow's own bacnet-discovery-api.md (section 3b) for the
full writeup, including the one real gap worth knowing before you lean on
it: there's no default rate-limit tiering, so an unthrottled noisy point
with only his_collect_cov set will publish (and therefore get
evaluated) on every single change.