Windrow - Periodic Discovery and Credentials
Mirrors Windrow's own docs/periodic-discovery-and-credentials.md —
Windrow is a sibling repo (github.com/jacobnash/Windrow); this page makes the worked
example reachable from here. Built for new-construction commissioning:
equipment shows up on the network over time, and a human shouldn't have
to remember to click "scan." windrow.api runs discovery on its own on a
timer, tracks every device either scan has ever seen — separate from
provisioned connections — and gives you somewhere to record a login if a
device needs one.
Code
- BACnet Who-Is scanning always runs (
--bacnet-discovery-interval, default 300s) — no subnet argument needed, it broadcasts on whatever interface--addressalready bound. - Modbus scanning is off by default. Modbus has no discovery protocol
of its own — "scan" means TCP-connect-sweeping a subnet on port 502 —
so there's no safe range to guess. Pass
--modbus-scan-cidr(repeatable) to turn it on for one or more subnets.
1. See what's been found
Code
Code
status is pending (seen, not provisioned), provisioned (a matching
connection exists — flips automatically, no extra call needed once you
POST /connections or POST /modbus/connections for it), or ignored (a
human dismissed it via PATCH /devices/{id}, survives future rescans).
2. Set a credential, if the device needs one
Neither BACnet nor Modbus has protocol-level auth — this is pure bookkeeping for whatever manual login the device's own surface needs (a gateway's local web UI, most commonly), recordable before any connection exists for it:
Code
Code
The plaintext password is shown once, in this response only. Every
later GET /devices (or GET /connections / GET /modbus/connections,
which support the same PATCH .../credential) redacts it:
Code
Stored encrypted at rest (Fernet, via the cryptography package), keyed by
the WINDROW_CREDENTIAL_KEY env var — generate one with:
Code
Setting a credential is bookkeeping only — nothing here logs into the device with it. That's deliberately out of scope; there's no protocol handshake to wire it into yet.
3. Default-credential check
The first time a Modbus device is seen as pending, windrow.api
automatically tries a short list of common defaults (admin/admin,
admin/password, root/root, …) as HTTP Basic Auth against the device's
own address, on ports 80 and 443 — GET only, non-destructive, meant to
catch equipment still on factory defaults during commissioning:
Code
BACnet devices always show default_credential_flag: null. BACnet has
no HTTP-login concept of its own, so there's nothing to check — this is
explicit, not a silently-skipped feature. Re-run the check later (e.g.
after changing the device's password) with:
Code
Known gap: HTTP Basic Auth only. Real gateway firmware more often uses a form-based admin login, which this doesn't catch — would need per-vendor knowledge, out of scope for a basic check.
4. Modbus: discover and provision
Modbus has no self-describing object list like BACnet's — register
addresses are opaque and vendor-documented, so you supply {label: address} directly instead of a /learn step:
Code
Code
vendor/product_code/revision come from Modbus function 0x2B/0x0E
(Read Device Identification) where the device implements it — null on a
device that doesn't is a normal result, not an error.
Code
Same GET/DELETE .../{id} and PATCH .../{id}/credential shape as
BACnet connections.
Known v1 limitations
- Same-host broadcast quirk as
/discover. A locally-originated BACnet Who-Is broadcast doesn't reliably loop back to another process on the same machine (macOS/BSD networking behavior) — the periodic BACnet scan can look like it's finding nothing if you're testing against a mock device on the same host. Works normally against real devices on a real network. Verified live: this is genuinely non-deterministic on a single host, not a bug in the scan loop itself (confirmed by drivingdevice_registry.reconcile_bacnet()directly against a real, reliable directed discovery call — the reconciliation logic behaves correctly every time; only the same-host broadcast delivery is flaky). - One shared poll interval per Modbus connection, not per-point like
BACnet connections support (
his_collect_covetc.) — nothing asked for that yet, and Modbus's opaque register model doesn't get much from it. - No default-credential check for BACnet — see above, not a gap so much as "the check has nowhere to point itself."
- No file locking on
windrow-devices.json/windrow-modbus-connections.json— same accepted single-writer assumption asconnections.json.
Real bugs this was verified against, not just assumed to work
- Device-registry reconciliation never matched a provisioned connection
back to its discovered device.
discover_devices()'s ownaddressfield never carries a port ("no port — the standard BACnet/IP port 47808 is implied"), but a connection'sdevice_addressfield commonly does ("192.168.128.63:47808", matching every worked example in this repo) — the two never compared equal. Fixed by normalizing on the host portion before matching. Found by actually provisioning a connection against a live mock device and watchingstatusnever leavepending, not by reading the code. - An unclosed
AsyncModbusTcpClientstalls process shutdown indefinitely. pymodbus's async client spawns its own internal "transport reconnect" background task; if nothing callsclient.close()before the owningasyncio.run()call tears down, that task doesn't respond to cancellation in time and the whole shutdown hangs forever. Reproduced reliably with two sequentialasyncio.run()calls in one process (exactlywindrow.api's create-a-connection-then-restart shape); fixed with an explicitModbusConnectionManager.close()called fromapi.py's shutdown path (and from every test's teardown). - pymodbus 3.14's real method is
read_device_information(device_id=...), notread_device_identification— confirmed viainspectagainst the installed package rather than guessed from older docs/examples.